If you want to print out all the setpoint parameters for a PSS500 controller, do the following steps in sequence:
Procedure
- Turn off the yellow breaker switch on control panel
- Open the controller lid and toggle the EPROM switch (located under “CAUTION” on the control board) from OPER to CAL
- Turn the yellow breaker switch back on
- The display will now show “HIT ANY BUTTON”
- Warning! When in “EEPROM DIAGS”, do not hit [ENTER] when “SET DEFAULT VALUES” is displayed. This will result in the loss of all setpoints and calibrations!
- Use the [Arrow] and go to “EEPROM DIAGS”. Hit [ENTER]
- [Arrow] to “PRINT MACHINE VALUES”. Hit [ENTER]
- The printer will now print the setpoints
- Turn off the yellow breaker switch
- Switch the EPROM from CAL to OPER
- Turn the yellow breaker switch back on
Have a question or having difficulties? Talk to Dave Schall, our PRIMUS sterilizer expert who is here to assist you anytime at 877.679.7800 extension 1212 or email at dschall@spire-is.com.